Boiler fans & process circulation
Combustion air and circulation demand vary with process load. Drive control must remain subordinate to the boiler’s certified combustion and safety system.

Load characteristics & existing operating problems
Boiler draught fans, forced-draught fans and circulation pumps follow thermal load but are constrained by minimum flows and purge requirements. Dampers may waste energy, yet unstable combustion, fouled heat-transfer surfaces and water-circuit problems cannot be solved by a drive alone. Boiler specialists must establish the safe envelope before discussing motor-speed changes; electrical control is not a combustion-system retrofit.
- Boiler / process controller
- verified speed command
Hailing 790drive- fan or circulation pump
System composition & control sequence
The existing combustion/process controller retains purge, ignition, fuel and trip permissions. The drive follows a verified speed command only. Review minimum air/water flow and fault response with boiler interlocks; loss of reference cannot simply default to minimum speed. Existing low-flow and pressure protection must remain active when variable-speed control is added.
Selection inputs & control requirements
Identify minimum air and water flow, furnace-pressure limits, pre/post-purge sequences, motor ratings and control interfaces. Confirm all permissives with the boiler equipment supplier.
| Data to collect | Why it matters | Reference |
|---|---|---|
| Thermal duty and minimum flow | Establish safe modulation limits and prevent low-flow damage or invalid combustion conditions. | Explicit boiler-manufacturer and process-design requirements. |
| Fan/pump curves and motors | Distinguish airflow pressure, furnace pressure and circulation head. | Equipment curves, nameplates and site measurements. |
| Purge, permissions and fault mode | Keep sequencing consistent with original safety protection. | Original boiler controls; the drive is not a burner-management system. |
| Interface and backup arrangement | Verify commands and fault feedback and prevent unsafe bypass switching. | 790/3000/7000 are candidates; verify actual terminals and switching circuits. |
Capability and safety boundaries
A VFD is not a burner-management system.
Application scenario / design example
APPLICATION SCENARIO / SELECTION EXAMPLEAssume a process-boiler circulation pump runs at fixed speed with throttling at low thermal demand. Obtain the boiler minimum-flow requirement and pump curve, then measure flow, differential pressure and motor duty. If modulation is permitted, the original controller issues a bounded speed demand and retains the low-flow trip. Boiler risk assessment determines drive-fault handling. Trial records separate heat service and electrical consumption across thermal loads without claiming reduced fuel use or guaranteed boiler efficiency.
Commissioning & acceptance checks
Validate purge permissions, minimum flow, control-signal failure and safe stop/restart with the boiler supplier.
- Boiler personnel first confirm instruments, interlocks and permissions, preserve the original control strategy and review drive circuits under agreed maintenance/trial conditions.
- At permitted thermal loads, record flow, pressure, current and temperature and check minimum flow and transients. Combustion adjustments remain with the appropriate specialist.
- Jointly verify signal failure, low flow, fault stop and power recovery using approved procedures, ensuring speed control cannot bypass purge or restart permissions.
Assessing energy and operating value
Relate fan/pump electricity to the same thermal service, flow and environmental conditions, measuring fuel and electricity separately. Isolate effects from cleaning, heat-load changes and water temperatures. Reduced heat delivery or shortened required purges cannot be counted as an efficiency benefit.




