VFD overheating: cabinet cooling methods and how to size a ventilation fan

Why heat shortens inverter life, the three ways to cool a drive cabinet, a rule of thumb for fan airflow, and the daily checks that keep temperatures under control.

VFD overheating: cabinet cooling methods and how to size a ventilation fan

Frequency inverters operate within a specified ambient temperature range. Failure rates rise sharply with temperature and service life falls just as quickly: as a rule of thumb, every 10 °C rise in component temperature halves reliability. Heat management is therefore one of the most effective ways to keep a drive running.

Where the heat comes from

Almost all of the losses (about 98%) occur in the main circuit; the control circuit accounts for about 2%. Total losses are typically 4–5% of the drive rating. Of these, the inverter stage accounts for about half, the rectifier and DC link about 40%, and control and protection circuits the remainder. IGBT switching losses rise with carrier frequency, so a higher carrier frequency means more heat.

Three ways to cool a drive cabinet

1. The drive's built-in fan

Suitable for small drives in a cabinet with few other heat sources. Install the drive as specified so that its own fan can move heat out through the enclosure.

2. Cabinet ventilation fans

The most common method for larger cabinets with several drives or other heat-producing components. A useful sizing rule is that removing 1 kW of losses needs about 360 m³/h of air. Taking losses as 5% of the drive rating:

Fan airflow (m³/h) = drive rating (kW) × 5% × 360 m³/h per kW

Example: a 90 kW drive needs 90 × 5% × 360 = 1,620 m³/h of airflow. Select the fan model from this figure.

3. Cabinet air conditioning

Used where the environment is especially demanding or for very large drives. Cost, size and condensate drainage need to be considered at the cabinet design stage.

Other factors

  • Above 1,000 m altitude the air is thinner, so cooling capacity must be increased.
  • Keep the carrier frequency no higher than the application needs.
  • Leave the ventilation clearances given in the manual and install drives vertically.
  • In dusty industries such as coal, clean the cabinet and the drive air ducts regularly.

Daily temperature checks

  1. Listen for changes in motor sound or vibration.
  2. Check the ambient temperature; around 25 °C is ideal.
  3. Confirm the drive fan runs and the airflow path is clear.
  4. Use an infrared thermometer on the heatsink and check for any burning smell.
  5. Clean cabinet inlet filters routinely.
  6. During annual maintenance, open the drive and clean boards, modules, capacitors and reactors with a brush or vacuum.
  7. Replace the cooling fan or its bearing every 2–3 years depending on operating hours.

SEND INQUIRY NOW

Call or WeChat us directly, or tell us your motor, supply, PV array or application requirements below and we will reply with a product recommendation.

Headquarters · China

Qingdao Hailing Electric Co., Ltd.

CallEmail
Pakistan Company

VICTORY ENERGY TECHNOLOGIES (PVT) LIMITED

Industrial control room
Qingdao Hailing Electric Co., Ltd.No. 5 Yuanzhong Road, Jiaobei, Jiaozhou, Qingdao, China