Permanent-magnet synchronous motor (PMSM) setup: wiring and open-loop parameters
How to wire and commission a permanent-magnet synchronous motor on a Hailing drive in open-loop vector mode, including dynamic auto-tuning and the back-EMF check.

Permanent-magnet synchronous motors (PMSM) are used increasingly on compressors, fans and pumps for their efficiency. They must be identified as synchronous motors and tuned before running. The steps below are the open-loop vector setup used on Hailing drives; parameter groups are shown as F0/F1 (equivalent to P0/P1).
1. Wiring
Connect drive terminals U, V, W to motor terminals U, V, W.
2. Open-loop parameter settings
| Step | Parameter | Setting |
|---|---|---|
| 1 | F0-01 | 0: open-loop vector |
| 2 | F0-10 | Motor rated frequency (maximum frequency) |
| 3 | F0-12 | Motor rated frequency (upper limit frequency) |
| 4 | F1-00 | 2: synchronous motor |
| 5 | F1-01 | Motor rated power |
| 6 | F1-02 | Motor rated voltage |
| 7 | F1-03 | Motor rated current |
| 8 | F1-04 | Motor rated frequency |
| 9 | F1-05 | Motor rated speed |
3. Dynamic auto-tuning
- With the parameters above set, select F1-37 = 12 and press RUN on the panel to start dynamic auto-tuning.
- After tuning, read F1-20 (learned back-EMF) and compare it with the theoretical value from the motor data. A difference of ±10 V is normal. If the learned value is more than 10 V below the theoretical value, contact Hailing for confirmation before running.
- Set the reference frequency to the rated value, press RUN and check the no-load current.
For asynchronous motors, see motor parameter auto-tuning.