Controlling a Hailing VFD over Modbus RTU (RS485): addresses and commands
The RS485 bus structure, function codes 0x03 and 0x06, and the registers for run commands, frequency setpoint, status and fault code on Hailing general vector drives.

Hailing general vector drives provide an RS485 interface (via the RS485 expansion card) and act as a Modbus-RTU slave. A PLC, HMI or PC can start and stop the drive, change parameters and read status and fault information.
Bus structure
- One master, several slaves. The master (PLC, HMI or PC) starts every exchange.
- Slave addresses 1 to 247; 0 is the broadcast address. Each address on the network must be unique.
- Asynchronous serial, half-duplex. A silent interval longer than 3.5 characters marks the start of a new frame.
- Broadcast messages are not answered; addressed messages return a response frame.
Function codes
- 0x03 read words. Up to 12 consecutive parameters can be read at once, without crossing the end of a parameter group.
- 0x06 write one word.
- Only word-type data is supported; byte and bit access are not.
Key registers
| Address | Access | Meaning |
|---|---|---|
| 2000H | Write | Control command: 1 forward run, 2 reverse run, 3 forward jog, 4 reverse jog, 5 coast to stop, 6 decelerate to stop, 7 fault reset |
| 1000H | Write | Communication setpoint, −10000 to 10000 = −100.00% to 100.00% (frequency, torque limit, PID setpoint and similar sources set to "communication") |
| 3000H | Read | Operating status: 1 forward run, 2 reverse run, 3 stopped |
| 8000H | Read | Current fault code |
| 2001H | Write | Digital output control (DO1, DO2, relays, FMR, virtual outputs) when the output function is set to communication control |
| 2002H / 2003H / 2004H | Write | AO1, AO2 and FMP high-speed pulse output when set to communication, 0–7FFF = 0–100% |
| 70xxH | Read | U-group monitoring values; for example U0-11 is 700BH |
Setting up the drive
- Fit the RS485 card and wire A/B with screened twisted pair; terminate the end of the bus.
- Set the slave address, baud rate and data format in the PD (communication) group to match the master.
- Set the command source P0-02 = 2 (communication) to start and stop over the bus.
- Set the frequency source to communication if the master supplies the speed setpoint through 1000H.
- If a user password (PP-00) is set, verify it over communication before parameter initialisation.
Hailing soft starters also support RS485/Modbus with up to 64 starters on one bus.