Solar pump inverter sizing: matching the PV array to the HL710 controller
How to choose an HL710 solar pump controller and PV array: array power of 1.2–1.6 times pump power, open-circuit voltage limits, MPPT range and when to go one size up.

A solar pumping system consists of the PV array, the solar pump controller, a combiner box and the pump. It is widely used for irrigation and water storage in areas without a reliable grid. Correct sizing comes down to three checks: controller power, PV array power and PV string voltage.
1. Controller power
Start from the pump motor's rated power and current. For deep-well pumps, or where the output cable to the pump is long, select the controller one size larger than the pump. The configuration examples in the HL710 catalog follow this rule: a 2.2 kW deep-well pump uses an HL710-004GT4, a 3.7 kW pump an HL710-5R5GT4.
2. PV array power
Depending on the solar conditions in the region, the PV array power should be 1.2 to 1.6 times the pump power. The HL710 datasheet gives recommended array power for each controller, for example:
| Controller | Rated output | Recommended PV array |
|---|---|---|
| HL710-2R2GT2 / 2R2GT4 | 2.2 kW | 2.7–3.5 kW |
| HL710-004GT4 | 3.7 kW | 4.8–6.4 kW |
| HL710-5R5GT4 | 5.5 kW | 6.6–8.8 kW |
| HL710-7R5GT4 | 7.5 kW | 9–12 kW |
| HL710-011GT4 | 11 kW | 13.2–17.6 kW |
| HL710-015GT4 | 15 kW | 18–24 kW |
| HL710-022GT4 | 22 kW | 26.4–35.2 kW |
| HL710-045GT4 | 45 kW | 54–72 kW |
| HL710-110GT4 | 110 kW | 132–176 kW |
3. String voltage
| Version | Max. PV input (Voc) | Recommended MPPT voltage | Pump supply |
|---|---|---|---|
| GT2 | 450 V DC | 275–380 V DC | 220 V three-phase output |
| GT4 | 800 V DC | 500–750 V DC | 380 V three-phase output |
Choose the number of modules in series so that the string operating voltage sits in the recommended MPPT range, and the open-circuit voltage at the lowest expected temperature stays below the maximum input. Module Voc rises in cold weather, so allow margin. Add parallel strings to reach the required array power.
Example from the HL710 catalog
For a 5.5 kW deep-well pump: controller HL710-7R5GT4 with 38 modules of the catalog example type, 19 in series (571.9 V) × 2 strings, 7.6 kW in total, through a 4-into-1 combiner box.
Before ordering, tell us
- Pump type, rated power, voltage and current, and required flow and head
- PV module datasheet (Voc, Vmp, Isc, temperature coefficient)
- Site location and lowest expected temperature
- Whether a grid or generator backup input is needed